In the IGSS software, there is an object called System. This object is used by the IGSS system to generate alarms under specific conditions.
A system alarm is triggered from the System object under the following four conditions.
Let’s look at the alarm messages displayed for each situation.
1. Insufficient hard disk space
When the IGSS system registers a low level of hard disk space, then
the System alarm is triggered
after activating the IGSS Starter
. The message looks like
this:
Figure 1: Basic System alarm message
You must then shut the IGSS system down and remove enough files from the hard disk to free up at least 20% of hard disk capacity. Then start the IGSS system up again.
The occurrence of this alarm by itself is rare because hard disk capacity nowadays is hardly ever exceeded by normal SCADA systems.
However, the alarm is triggered in connection with the presence of other conditions, which need attention by the user. These are described in the next two cases.
2. Error in connection with the IGSS application’s report folder: cannot find the report folder
When this situation occurs, the ALL
LOGGING STOPPED alarm, as shown in Figure 1 above, will be triggered
as well as a dialog box with an alarm message. When this happens, the
This alarm arises typically when configuring a multi-user system and looks like this:
Figure 2: Cannot find the report folder warning
This message indicates that the path to the IGSS application’s report folder has somehow been incorrectly keyed in. Therefore, check first in the System Configuration module on the server PC on the Configuration tab under Report folder. Check the following two things:
This should remedy the problem.
3. Error in connection with the IGSS application’s report folder: access denied
When this situation occurs, the ALL LOGGING STOPPED alarm, as shown above, will be triggered as well as a dialog box with an alarm message. When this happens, the ALL LOGGING STOPPED alarm can be ignored as the true cause of the alarm state.
This alarm arises typically when configuring a multi-user system and looks like this:
Figure 3: Access denied warning
This message indicates that sharing and/or setting of permissions on the report folder has not been correctly carried out. Do the following:
This should remedy the problem.
4. Display an Event in the Active Alarms list
This last example of the triggering of a System alarm is not related to an error situation. Here the System object is used to display the occurrence of an Event in the Active Alarms list. For a detailed explanation click this link Event.